原装进口美国GET5000系列二氧化碳温度传感器变送器
编辑:admin 时间:2010-10-16 17:24:33 来自:传感器网
T5000 Airestat CO2 &Temperature Transmitter
原装进口美国GET5000系列二氧化碳温度传感器变送器

The Telaire® T5000 series Airestat™ CO2 and temperature transmitter is a low-cost wall-mounted sensing solution for demand-controlled ventilation.
The Airestat provides an intuitive VLI (Visual Limit Indicator) display for CO2 thresholds, a passive temperature output (20k thermistor), and a standard analog 0 to 10 volt signal to maintain air quality in enclosed spaces (such as school classrooms, offices, gymnasiums and theaters).
Features
原装进口美国GET5000系列二氧化碳温度传感器变送器技术参数
Low-cost
Reliable (15 years of low-cost infrared sensor manufacturing)
Pre-calibrated
Maintenance free (calibration maintained with patented ABC Logic)
Flexible configurations (see matrix, page 2)
Intuitive VLI display
Two available outputs: analog 0 to 10V and passive temperature (20K thermistor)
User-definable thresholds
RoHS and WEEE compliant
Lifetime calibration warranty
The Telaire T5000 Series Airestat CO2 and temperature transmitter is a low-cost wall-mounted sensing solution for demand-controlled ventilation.
The Airestat provides an intuitive VLI (Visual Limit Indicator) display for CO2 thresholds, a passive temperature output (20kΩ thermistor), and a standard analog 0 to 10 volt signal to maintain air quality in enclosed spaces (such as school classrooms, offices, gymnasiums and theaters).
T5000 Airestat CO2 &Temperature Transmitter Sampling Method
Non-dispersive infrared (NDIR), gold plated optics, (with Telaire’s patented ABC Logic self calibration algorithm). Diffusion sampling.
Measurement Range
0 to 2,000 ppm factory calibrated.
Accuracy
± 75 ppm @ 72°F (22°C) when compared with a factory reference or 10% of reading, whichever is greater*
Temperature Dependence
0.2% FS per °F (°C)
Stability
<2% of FS over life of sensor (15 years typical)
Non-Linearity
<1% of FS
Pressure Dependence
0.13% of reading per mm Hg
Calibration Interval
Not required*
Response Time
3 to 5 minutes for 90% step change.
Warm up Time
• <2 minutes (operational)
• 10 minutes (maximum accuracy)
Operating Conditions
• 32°F to 122°F (0°C to 50°C)
• 0 to 95% RH, non condensing
Storage Conditions
• -4°F to 158°F (-20°C to 70°C)
• 0 to 95% RH, non condensing
Temperature
NTC 20k thermistor
Output
• Analog: 0 to 10V (100 Ω output impedance)
Connections
Screw terminals for 18 to 28 AWG
Power Supply Requirements
18 to 30 VAC RMS, 50/60Hz or 18 to 42 VDC, polarity
protected
Power Consumption
1.75 VA average, 2.75 VA peak
Agency/Certifications
FCC Part 15 Class B, CE, RoHS, WEEE
Warranty Term
18 months
* Note: Automatic Background Calibration, or ABC Logic, is a patented self-calibration technique designed to be utilized in applications where concentrations will drop to outside ambient conditions (approximately 400 ppm) at least four times in a 14-day period, typically during unoccupied periods. Full accuracy is achieved after two weeks of operation.